4 FAQs about How to open the site of the battery cabinet in the computer room
Where should a top terminal battery be installed?
(D) Top Terminal Batteries. Where top terminal batteries are installed on tiered racks, working space in accordance with the battery manufacturer’s instructions shall be provided between the highest point on a cell and the row or ceiling above that point. (E) Egress.
How much space do you need for a battery system?
Spaces about battery systems shall comply with 110.26. Working space shall be measured from the edge of the battery cabinet, racks, or trays. For battery racks, there shall be a minimum clearance of 25 mm (1 in.) between a cell container and any wall or structure on the side not requiring access for maintenance.
What are the requirements for a battery location?
Battery locations shall conform to 480.9 (A), (B), and (C). (A) Ventilation. Provisions appropriate to the battery technology shall be made for sufficient diffusion and ventilation of gases from the battery, if present, to prevent the accumulation of an explosive mixture. (B) Live Parts. Guarding of live parts shall comply with 110.27.
Does a battery room need egress?
Now, the ventilation must be appropriate for the type of battery used or for the battery technology involved. As well, now proper egress has been addressed. Section 480.9 (E) requires any personnel doors intended for entrance to, and egress from a battery room, to open in the direction of egress and be equipped with listed panic hardware.